Zone Status Messages
The table below describes the typical commands used to query the control panel for a Zone Status and the
zone’s partition. NOTE: The system can provide the status for zones 1 to 96 only.
Zone Status Request and Report Messages
Action String Definition
Zone Status
Request
08zs004B (CR-LF) The panel responds with a Zone Status Report.
Note: This message should be sent only when an initial
connection is made with the panel. It is not intended for use
as a ‘polling’ command. The panel can be programmed to send
System Notification Messages concerning zone status.
Zone Status
Report
68ZSD…00CC (CR-LF) The panel sends this message in response to a Zone Status
Request. The data portion of this message is 96 characters
(one character for each zone in order). Each character is the
sum of all applicable status values, expressed in hexadecimal
using ASCII characters 0-9 and A-F.
Status Values
0 Closed
1 Open
2 Trouble
4 Alarm
8 Bypassed
Example: a Zone Status Report for a system in which Zone 1
is Open, Zone 2 is Open, in Trouble, and Bypassed, and the
rest Closed, would begin 68ZS1B00…
Zone
Partition
Request
08zp0004E (CR-LF) The control panel responds with a Zone Partition Report.
Zone
Partition
Report
68ZPD…00CC (CR-LF) The panel sends this message in response to a Zone Partition
Request. The data portion of this message is 96 characters
long, one character for each zone in order. The value will be
from 0-8, with 0 meaning no partition assignment.
Example: a Zone Partition Report for a system in which Zone
1 is assigned to Partition 2. Zone 2 is assigned to no partition,
and Zone 3 is assigned to Partition 8, would begin68ZP208…